Magnetic Flow Meters

Introduction to Magnetic Flow Meters

A magnetic flow meter (mag flow meter) is a volumetric flow meter which does not have any moving parts and is ideal for wastewater applications or any dirty liquid which is conductive or water based. Magnetic flow meters will generally not work with hydrocarbons, distilled water and many non-aqueous solutions. Magnetic flow meters are also ideal for applications where low-pressure drop and low maintenance are required.

Learn more about magnetic flow meters

Principle of Operation

The operation of a magnetic flow meter or mag meter is based upon Faraday's Law, which states that the voltage induced across any conductor as it moves at right angles through a magnetic field is proportional to the velocity of that conductor.

Faraday's Formula

E is proportional to V x B x D where:

E = The voltage generated in a conductor
V = The velocity of the conductor
B = The magnetic field strength
D = The length of the conductor


To apply this principle to flow measurement with a magnetic flow meter, it is necessary first to state that the fluid being measured must be electrically conductive for the Faraday principle to apply. As applied to the design of magnetic flow meters, Faraday's Law indicates that signal voltage (E) is dependent on the average liquid velocity (V) the magnetic field strength (B) and the length of the conductor (D) (which in this instance is the distance between the electrodes).In the case of wafer-style magnetic flow meters, a magnetic field is established throughout the entire cross-section of the flow tube. If this magnetic field is considered as the measuring element of the magnetic flow meter, it can be seen that the measuring element is exposed to the hydraulic conditions throughout the entire cross-section of the flow meter. With insertion-style flow meters, the magnetic field radiates outward from the inserted probe.

Magmeter Selection

The key questions which need to be answered before selecting a magnetic flow meter are:
  • Is the fluid conductive or water based?
  • Is the fluid or slurry abrasive?
  • Do you require an integral display or remote display?
  • Do you require an analog output?
  • What is the minimum and maximum flow rate for the flow meter?
  • What is the minimum and maximum process pressure?
  • What is the minimum and maximum process temperature?
  • Is the fluid chemically compatible with the flow meter wetted parts?
  • What is the size of the pipe?
  • Is the pipe always full?


Choose the right mag flow meter

Top
Insertion magmeter Insertion Magmeters
These versatile, simple-to-install flow meters deliver accurate flow measurement over a wide dynamic range in pipe sizes ranging from 0.5 to 8", satisfying the requirements of many diverse applications. FMG3000 Series magmeters offer a variety of output options for use with OMEGA flow instrumentation that has a frequency or 4 to 20 mA output. Flow velocity measurement is compensated for temperature via an integrated temperature sensor.
In-Line magmeter In-Line Magmeters
The FMG600 Series electromagnetic flow meters are designed for measurement of conductive liquids. The FMG600 magmeters have no moving parts and a PTFE lining, they can handle applications involving wastewater, pulp, food, and slurries. Standard outputs include analog, frequency, and RS485 communications. Optional sanitary tri-clamp mounting allows the use of the FMG600 flow meters in applications not previously open to magmeters. Local- and remote-display models are available.
Low Flow Magmeters Low Flow Magmeters
The FMG-2000 has no moving parts, and electrodes are designed to discourage fouling. This magmeter requires no maintenance in applications where debris would impede mechanical meters. There are no parts to wear out. Minimal straight pipe requirements allow FMG-2000 Series meters to be used in piping configurations where there is little space between the meter and an elbow. FMG-2000 Series meters are rated IP68 for applications where the meter may be under water up to a depth of 3 m (10') for prolonged periods of time. Rate and total indication are standard. Rate and total units and pulse output are settable via the front panel touch key pad by the user.

FAQ

Top

Insertion Magmeters

Insertion type meters offered by Omega have a standard 2 NPT or fit into a specific size fitting. The FMG-550 Series are designed for 2" to 48" in size with a flow rate of 0.05 to 10 m/sec (0.15 to 33 ft/sec). The FMG-550 Series offers an analog output with an integral display for flow rate and totalization. The FMG3000 series offers corrosion resistant materials for pipes from 0.5 to 8". These insertion type flow meters are ideal for large pipe applications.

Minimum Conductivity:

5 to 20 microSiemens/cm

Installation Considerations

Select a location for the sensor where the flow profile is fully developed and not affected by any disturbances. A minimum of 10 pipe diameters of straight run upstream and 5 diameters downstream is recommended. Some situations may require 20 pipe diameters or more upstream to ensure a fully developed turbulent flow profile. The insertion magmeter is sensitive to air bubbles at the electrodes. If there is any question that the pipe is absolutely full, mount the sensor at a 45 to 135 degree angle.

Grounding Requirements

For many years, sensors used in high-reliability applications, such as those used in aerospace and military applications, relied upon connectors such as the Mil-C-5015 or MIL-C-38999 connectors that provided high reliability and secure connections but at a high price. With the expanded use of industrial automation systems, however, the number of sensors used have increased dramatically, driving the need for a reliable, cost effective connection system for these sensors.

In-Line Magmeters

The In-Line type magnetic flow meters offer a higher accuracy. They can be as accurate as 0.5% of the flow rate. The insertion styles offer a 0.5 to 1% accuracy. OMEGA's FMG-600 series In-Line flange and wafer style meters offer higher flow rates of 1 to 10 m/sec. These In-Line meters are offered in pipe sizes up to 12".

Installation Considerations

In-Line flow meters do not require as much straight pipe as the insertion styles. A minimum of 5 to 10 pipe diameters of straight run upstream and 1 to 2 diameters downstream is recommended. In vertical pipe runs, flow should always run up and not down. These flow meters are very sensitive to air bubbles. The magmeter cannot distinguish entrained air from the process fluid; therefore, air bubbles will cause the magmeter to read high.

Low Flow Magmeters

These low flow mag flow meters are also In-Line and offer 3/8 to ½ NPT connections. The FMG200 series offer flow rates down to 0.38 LPM (.1 GPM). A digital display with relay and analog outputs are standard.