Capteurs de Pression de Haute Précision, Silicium Micro-Usiné

0 to 100 psi, Gauge, 4 to 20 mA, 1/4" NPT Male, MIL-26482-I 10-6P, (-49 to 240 °F)

C$1,152.35

Article# PX429-100GI

Remises de volume disponibles
Calendrier de remise sur volume
Quantité Prix unitaire
1-9 C$1,152.35
10-24 C$1,094.73
25-49 C$1,071.69
50-99 C$1,025.59
100+ C$1,002.54

En stock

Délai de livraison (si pas en stock): 6 semaines
0 to 100 psi, Gauge, 4 to 20 mA, 1/4" NPT Male, MIL-26482-I 10-6P, (-49 to 240 °F) PX429-100GI PX429-100GI
  • Pièces mouillées : acier inox 316
    Boîtier: acier inox soudé
  • Haute précision ±0.08% (BFSL) inclut les effets de linéarité, d'hystérésis et de répétabilité
  • Large gamme de compensation en température -29 à 85°C
  • Performance excellente en température: ±0.5% sur la plage de compensation
  • Certificat d'étalonnage raccordé à 5 points, inclus
  • Mesure des plages de basse pression de 10 in-H2O (25 mbar)
  • Pression absolue de 5 à 1000 psia
  • Temps de réponse rapide
  • Haute fiabilité et stabilité
  • Mesure pression absolue et jauge
  • Pression d'épreuve minimum de 300%

PX429-100GI Options de modèles

Voir tous les modèles

Modifiez ces spécifications pour commander un modèle différente. Toutes les combinaisons ne sont pas valides. Les options compatibles avec les sélections précédentes seront en gras.

* Les options en surbrillance ne sont pas compatibles. Veuillez sélectionner une combinaison différente ou cliquez sur le bouton CONFIGURER pour créer la vôtre.

Pressure Range
Pressure Type
Accuracy Value(compensated range)
Output Signal
Electrical Output
Pressure Port Type
Connection/Termination
Operating Temperature Range
Additional Features
Accuracy Class
Pressure Port Size


Description

Les capteurs de haute précision piézorésistifs Omega ont fait leurs preuves durant plus de 25 années dans des applications de haute performance commerciale et aéronautique. La technologie piézorésistif utilise des jauges de contrainte implantées dans une membrane stable en silicium. La membrane est coupée en dés, chacun contient un pont de jauge de contrainte. Il est protégé du milieu extérieur par un boîtier étanche en acier inoxydable fermé par un joint métal à verre et une membrane en acier inox.

La pression appliquée sur la membrane est transférée à l’élément sensible par un petit volume d’huile silicone. Cette construction assure un transducteur robuste doté d’une précision excellente, une bonne stabilité et les effets thermiques faibles. Sa robustesse est assurée par notre conception unique d'une enceinte de confinement secondaire de fluide en cas de rupture de membrane.

Chaque capteur est sévèrement testé en pression et température. Les capteurs sont étalonnés avec des appareils de haute précision, et livrés avec un certificat d’étalonnage raccordé à 5 points. La fiabilité de l'élément de capteur sur base piézorésistive donne une excellente stabilité en long terme, une bonne répétabilité et les effets thermiques très faible et pour le prix d’un capteur de pression moins performante. En standard les caractéristiques de l'PX409 comprennent la protection de l'électronique et de l'élément sensible contre l'inversion de polarité, EMC et les fluctuations de tension d'alimentation. Les classements de Sécurité Intrinsèque et CSA sont disponibles en option.

Les gammes de produits les plus courants sont stockés pour une livraison immédiate. D'autres configurations sont disponibles dans des délais courts.



Utilisez le tableau de "Construction d'une Référence" ci-dessous pour obtenir les caractéristiques complètes de ces produits.
loading all models
loading all reviews
Rated 5 out of 5 by from Top notch The quality of the signal and the precision are excellent. Also, the build quality is also very good.
Date published: 2023-02-24
Rated 5 out of 5 by from Great Product Great quality and speedy service, we will definitely buy from them again.
Date published: 2023-12-08
Rated 5 out of 5 by from Reliable sensors Very liable sensor. Has been our standard design for decades
Date published: 2023-11-25
Rated 5 out of 5 by from Great piece of equipment. Durable and reliable sensor. Arrived fairly quickly. A great choice when precise measurements are required.
Date published: 2023-09-18
Rated 5 out of 5 by from Quick Delivery Estimated restocking time of 4 weeks but got it in two! Excellent quality sensor
Date published: 2023-07-27
Rated 5 out of 5 by from High accuracy High accuracy and easy to mount it into experimetn
Date published: 2023-05-01
Rated 5 out of 5 by from Great Device These are fully functional and very easy to set up and use.
Date published: 2023-04-20
Rated 5 out of 5 by from Exactly what I paid for! Transducer is exactly what was expected. Packaging and documentation were perfect as well!
Date published: 2023-04-01
  • y_2024, m_4, d_23, h_5
  • bvseo_bulk, prod_bvrr, vn_bulk_3.0.41
  • cp_1, bvpage1
  • co_hasreviews, tv_0, tr_12
  • loc_en_CA, sid_PX429-100GI, prod, sort_[SortEntry(order=HELPFULNESS, direction=DESCENDING), SortEntry(order=POSITIVE_FEEDBACK, direction=DESCENDING), SortEntry(order=SUBMISSION_TIME, direction=DESCENDING)]
  • clientName_omega
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getReviews, 3ms
  • REVIEWS, PRODUCT
loading all QA

Does the pressure transducer have a specific install orientation? Any problems with a horizontal verses vertical install?

Asked by: mike_mcc
Typically the readings are not effected by orientation. You may see a shift in the readings on the very low pressure range (0 to 10"H2O and 0 to 1 PSI) if you change orientation but you should be able to calibrate that out in your readout device.
Answered by: Applicatrions Engineer JK
Date published: 2021-02-11

What is the resolution limit on this device? I'm interested in your 0-2 bar sensor and what the lowest pressure value it is able to measure accurately.

Asked by: Ben_
Resolution would depend on how small of a signal change the instrumentation used to read the 0 to 10VDC output can resolve. The sensor will read from 0 to 2 bar but the lower 10% of the range (0 to 0.2 bar) would end to be less accurate
Answered by: Applicatrions Engineer JK
Date published: 2022-03-01

Are the high accuracy transducers rated for use with hydrogen?

Asked by: jrea98
We do not recommended using our transducers in a hydrogen application due to embrittlement of the wetted parts when exposed to hydrogen
Answered by: Applicatrions Engineer JK
Date published: 2022-02-10

Hi, we have a PX409-16BI transmitter that we are developing a validation procedure for. Stated zero and span tolerances are +/- 0.5% FS typical with a +/- 1% FS maximum. Which should I use for validation? (BSL is not a validation tolerance)

Asked by: John314
You would use the +/- 1% FS max
Answered by: Applicatrions Engineer JK
Date published: 2020-06-12

When you say accuracy, are you referring to the resolution or the measurement, or the actual measurement accuracy? What are the respective values of each?

Asked by: Julian
Thank you for contacting Omega. The PX409 is a full analog path sensor, meaning it's resolution is essentially infinite. The accuracy we specify details the uncertainty of the output. We specify the combined uncertainty contributed by non-linearity, repeatability, and histories.
Answered by: Jane
Date published: 2019-02-12

I have to return a couple of these pressure sensors to a client overseas (UK). But before my company can ship them, we need to know the ECCN export number. Please supply the ECCN for these items... PXM419-070BA10V. Thank you.

Asked by: ziggy19
Thank you for contacting Omega engineering, for export related question kindly send an email to exportcompliance@omega.com. Thank you.
Answered by: SAE DV
Date published: 2019-11-23

I would like to purchase the Item# PX429-001GI, which shows a pressure range of 0-1 psi. How can I determine the resolution (ie x.xxxx psi) for the pressure reading that I will be able to get from the transducer?

Asked by: Briananana
This would depend on how small of a signal change the instrumentation you are using to read the signal can detect.
Answered by: Applicatrions Engineer JK
Date published: 2023-05-19

Are 2-D or 3-D CAD drawings available for the PX459-030AI pressure sensor?

Asked by: NickEng
There are no CAD drawings currently available for the PX459 pressure transducers
Answered by: Applications Engineer JK
Date published: 2023-02-16

What is the average pressure drop across one of these transducers?

Asked by: Ingenia
There is no pressure drop rating for this sensor.
Answered by: Applicatrions Engineer JK
Date published: 2023-06-13

What is the difference between the PX409-030AI-EH and PX409-030AI Models?

Asked by: Maxx
Maxx, the -EH models have a 0.05% BFSL static pressure accuracy, whereas the models without -EH will have a 0.08% BFSL accuracy.
Answered by: SAE DV
Date published: 2023-10-11

I'm trying to locate the free software that accompanies this product, could you please provide the link?

Asked by: Joe_
Hello, and thanks for connecting with us. The software icon, for the free software download, is located in under the bullet points (before the Description copy) on the product page https://www.omega.com/pptst/PX409-485_PXM409-485.html Please contact our Tech Support if have any further questions.
Answered by: Jane
Date published: 2019-10-09

I have PX409-050A5V, what is the transfer function y=mx+b of Pressure vs Voltage output?

Asked by: DannyP
Thank you for your inquiry, the information you're requesting will be located on the certificate of calibration.
Answered by: rkent
Date published: 2022-04-08

It says that this sensor is recommended to be calibrated once a year, is the calibration procedure included with the sensor, or is calibration handled by a third party organization?

Asked by: John96
Thank you for your inquiry, we do not include a calibration procedure, however we do offer calibration services.
Answered by: rkent
Date published: 2021-12-09

I'm trying to locate the free software that is advertised for this product, could you please provide the link?

Asked by: UnderPressure
Thanks for being an Omega customer. The free software is available here for this product: ftp://ftp.omega.com/public/DASGroup/products/USBH/
Answered by: Jane
Date published: 2021-10-25

I have a PX409-3.5KGUSBH model transducer that currently reads absolute pressure. Can I calibrate the transducer in house to read relative gauge pressure instead?

Asked by: aaron1230
Thank you for your inquiry While the construction of a gauge or absolute sensor is fundamentally different, in this case where your sensor has a range of 3,500 psi A is so large it should be fine. This issue is that an absolute sensor has no way to react to changes in atmospheric pressure like a gauge sensor does. The typical worst-case limits in atmospheric pressure changes (if you don't change your elevation) are between 13.5 – 15.0 psi, or about 1.5 psi, this is only (1.5/3500*100) = 0.04% FS change for the sensor, smaller than the error band! You can safely ignore atmospheric pressure changes for this device and offset your device to represent a gauge pressure reading. hope this was helpful?
Answered by: application engineer je
Date published: 2022-08-03

We have pressure transducer model number PX409-050A10V, for which we'd like to know its leakage specs and/or hermeticity rating... is that data available please?

Asked by: Scottie
Thank you for your inquire Overpressure Absolute Pressure: 5 psia: 6 times span 2.5 psia to 1000 psia: 4 times span 1500 to 5000 psia: 10,000 psi maximum Secondary Containment Gage/Diff/Vac/Compound: 10 inH2O to 5 psi: To 1000 psi 15 to 1000 psi: To 3000 psi 1500 to 5000 psi: To 10,000 ps
Answered by: application engineer je
Date published: 2022-05-19

is the USB pressure sensor communication documented so it can be used with a language like LabVIEW? i would expect it shows up as a serial port and has a communication protocol to read values.

Asked by: VSI_
Thank you for your inquiry, Omega doesn’t support LabVIEW, but customers have told us they use our USBH sensors with LabVIEW : The easy-to-use ASCII data protocol of the USBH sensors can be handled with a standard LabVIEW VI like: Basic Serial Write and Read.vi. (While Omega gladly provides support for our .NET API, we cannot provide support for implementation as a part of LabVIEW). ). If you have any additional questions please contact our customer support department.
Answered by: rkent
Date published: 2022-04-15

I thought the sensor will come with a USB plug cable, but it doesn't. How should I connect the cable to a USB plug? What kind of USB plug should I get for it?

Asked by: Anonymous
There are two versions of the PX409 Pressure Transducers. One version as an analog output of millivolts, Voltage or Current. The other version has a high speed USB output. It appears you have the analog output version with would not have a USB connect on it. You would need to purchase a new PX409 with the part number ending in USBH. This unit has an attached cable with the USB connection on the end
Answered by: Applicatrions Engineer JK
Date published: 2021-05-07

Is there an interface document for available to guide customer developed software deisgn to interface with these sensors over a USB connection to a Linux microPC?

Asked by: NASA Life Support
There is no documentation available to guide you in software design for this device.
Answered by: Applications Engineer JK
Date published: 2023-04-06

Can these be used in helium systems?

Asked by: Greg2
All the parts of the PX409 series coming in contact with the media (wetted parts) are all 316 Stainless Steel. According to published chemical compatibility charts 316 SS is compatible with Helium
Answered by: Applicatrions Engineer JK
Date published: 2023-03-31

The PX409 spec sheet has a temp. comp. range of -29 to 85°C. It has a graph that shows the thermal affect in the compensated range. The thermal affect is greater than the accuracy of 0.08%. How must thermal affect be factored into the accuracy?

Asked by: ben06
Thank you for your inquiry. Please contact us directly at pressure@omega.com or 1-800-826-6342 to discuss this question.
Answered by: Applications Engineer Jk
Date published: 2023-03-07

What is the HSN (Harmonized System Nomenclature) code for the PX409-015CGUSBH and PX409-015GUSBH sensors?

Asked by: Klaus
Thank you for your inquiry, please contact us directly to obtain the HSN number
Answered by: rkent
Date published: 2022-10-14

Do you have documentation that describes the serial commands for the RS-485 interface (or the modbus registers)?

Asked by: ABH33
Thank you for your inquiry, we do offer a quick start manual for the RS485 sensors. This document can be found in the product manual section of our website ( PX409-485 and PXM409-485) if you require additional information please contact one of our Pressure engineers
Answered by: rkent
Date published: 2023-12-20

Hello, we need to measure up to 20 Bar pressure absolute. You offer a 17.5 Bar and 30 Bar option. Would the 17.5 Bar sensor report up to 20 Bar, and without causing damage?

Asked by: ZebraTech
Hello, Thank you for contacting Omega Engineering. If you want to measure 20 bar absolute you should not use the 17.5 Bar absolute unit, you may damage the diaphragm. Please go with the 30 bar absolute model. Thank you.
Answered by: SAE DV
Date published: 2019-10-11

What is the ambient storage temperature of this device? Is it the same or similar to the operating temperature?

Asked by: Maxx
These units have been tested to withstand an operating temperature of -49 to 240 Fahrenheit but not for prolonged periods. We do not have data on how the sensor will be affected if you store these transducers under those extreme conditions for longer periods of time.
Answered by: SAE DV
Date published: 2023-10-11

What is the weight for part# PX459-100GI

Asked by: ErJav
Thank you for your inquiry, this unit weighs less than 2 pounds
Answered by: rkent
Date published: 2022-11-01

I need to get accuracy and range on this. Can you please help

Asked by: Xochiltet
The three available accuracy ranges these sensors are 0.03%,0.05% & 0.08%. Accuracy is based on the full scale range of the sensor. Available pressure ranges from a low range of 0 to 10"wc up to 0 to 7500 PSI
Answered by: Applicatrions Engineer JK
Date published: 2019-11-21

I'm trying to locate the free software that is advertised for this product, could you please provide the link?

Asked by: Joe_
Thanks for your question. The free software is available here for this product: ftp://ftp.omega.com/public/DASGroup/products/USBH/
Answered by: Jane
Date published: 2022-02-01

What do you recommend if we exceed the proof pressure of 300%? Is the equipment still good to use? Would you recommend recalibration?

Asked by: mike21
Avoid exceeding the proof pressure rating of the sensor. You will damage the sensing diaphragm of the unit. It will most not be calibratable once damage
Answered by: Applicatrions Engineer JK
Date published: 2021-02-09

I am trying to locate the system requirements for the software.

Asked by: Jessie
The system requirements are: An up-to-date Windows 7, SP1; .NET Framework 4.5.2 (part of Microsoft’s automatic updates); USB 2.0 port. (USB 3 also works). Please contact our Tech Support if you need any further assistance.
Answered by: Jane
Date published: 2019-05-06
  • y_2024, m_4, d_23, h_5CST
  • bvseo_bulk, prod_bvqa, vn_bulk_3.0.41
  • cp_2, bvpage2n
  • co_hasquestionsanswers, tq_47
  • loc_en_CA, sid_PX429-100GI, prod, sort_[SortEntry(order=NUM_ANSWERS, direction=DESCENDING)]
  • clientName_omega
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getContent, 47ms
  • QUESTIONS, PRODUCT
ACCESSORIES
Extra mating DIN connector for PX419
C$48.73
76 In Stock
Mating connector (sold separately) for PX429S Series
C$54.51
0 In Stock
Pressure snubber for air/gaseous media
C$28.15
9 In Stock
Pressure snubber for water and light oils
C$27.83
0 In Stock
Pressure snubber for viscous liquids
C$28.15
0 In Stock
The M12 connectors can be attached to existing sensor or extension cables with a 6 to 8 mm cable diameter in the field by means of screw type connections
C$53.61
179 In Stock
5 m (16') PVC cable, straight 4-pin M12 female connector one end, flying leads one end, for all PX359 absolute range and gage ranges >100 psi
C$32.54
0 In Stock
M12 Extension Cable, 4 Wire PVC Cable, Right Angled Socket Connector One End and Flying Leads the Other, 5 meters long
C$32.54
21 In Stock
COMPATIBLE METERS AND ACCESSORIES
6-Digit strain meter with excitation
C$1,262.82
0 In Stock
6-Digit process meter for voltage and current models
C$1,334.12
0 In Stock
4-Digit Meter with excitation for mV/V Models
C$589.59
2 In Stock
4-digit precision process meter for use with voltage and current output models
C$589.59
3 In Stock
fr-CA
fr
Enregistrer la configuration