The DRSL-DC1 isolated repeater provides a competitive choice in terms of both price and technology for galvanic isolation of current signals to SCADA systems or PLC equipment. The unit provides isolation and 1:1 conversion of standard current signals.
The unit offers isolation between input, output and supply. Provides surge suppression and protects control systems from transients and noise. The DRSL-DC1 also eliminates ground loops and can be used for measuring floating signals. Low power consumption facilitates DIN rail mounting without the need for any air gap. Measurement ranges are factory calibrated. The unit operates over a wide temperature range from -25 to 70°C (-13 to 158°F).
SPECIFICATIONS CURRENT INPUT Measurement Range: 0 to 20.5 mA Functional Range: 0 to 23 mA Input Voltage Drop: <1.5 Vdc
CURRENT OUTPUT Signal Range: 0 to 20.5 mA (span) Load: 23 mA/600 Ω max Load Stability: ≤0.01% of span/ 100 Ω (span = 0 to 20 mA) Current Limit: ≤28 mA
GENERAL Supply Voltage (via Power Rail or Connectors): 16.8 to 31.2 Vdc Power Consumption: 0.8 W max Internal Consumption: 0.4 W typical/0.65 W max Isolation: Input/output/supply Isolation Voltage (Test): 2.5 kVac Isolation Voltage (Working): 300 Vac MTBF: >284 years, according to IEC 61709 (SN29500) Signal/Noise Ratio: >60 dB Response Time (0 to 90%, 100 to 10%): <7 ms Accuracy: <±0.05 % of span Temperature Coefficient: <±0.01% of span/°C EMC Immunity Influence: <±0.5% of span Extended EMC Immunity NAMUR NE 21, A Criterion, Burst: <±1% of span
ENVIRONMENTAL Operating Temperature: -25 to 70°C (-13 to 158°F) Storage Temperature: -40 to 85°C (-40 to 185°F) Calibration Temperature: 20 to 28°C (68 to 82°F) Relative Humidity: 0 to 95% RH non-condensing Protection Degree: IP20 Installation Area: Pollution degree 2 and measurement/overvoltage category II
MECHANICAL Dimensions: 113 H x 6.1 W x 115 mm D (4.4 x 0.24 x 4.5") Weight: 70 g (0.15 lb) approx DIN Rail Type: DIN EN 60715 - 35 mm Wire Size: 0.13 x 2.5 mm2/AWG 26 to 12 stranded wire Screw Terminal Torque: 0.5 Nm