- Wireless communication up to 1000 m* (3280’) outdoor and 100 m* (328’) indoor
- Wide range of measurements supported (4-20 mA, 0-10 V, mV, TC, and RTD)
- Data Assurance and logging up to 4096 readings per measurement
- Direct USB configuration for easy set-up
XW-EDA-PRO Options de modèles
Voir tous les modèlesModifiez ces spécifications pour commander un modèle différente. Toutes les combinaisons ne sont pas valides. Les options compatibles avec les sélections précédentes seront en gras.
*Les options en surbrillance ne sont pas compatibles. Veuillez sélectionner une combinaison différente.
Additional Features
Measurement Type
Number of Channels
Sensor Type
Sensor Connection
Form Factor
Range
Radio Frequency Compatibility
The XW Series Transmitters provide a wireless interface to a range of analog process signals and precision analog temperature (thermocouple and RTD) sensors. The radio is an IEEE 802.15.4 compliant transmitter operating at 2.4 GHz designed to transmit up to 1000 m* (3280’) and 100 m* (328’) to a ZW-REC coordinator.
The ZW-REC connects directly to an Ethernet network to serve active web pages and display the data. You can monitor and record data over an Ethernet network or the internet. These wireless devices are designed for demanding industrial applications indoors and harsh outdoor environments. The electronics are protected in a rugged weatherproof polycarbonate NEMA 4 (IP65) rated housing. The XW-EDA Transmitters come in two variants:
XW-EDA
The XW-EDA model support thermocouples, RTD’s, and precision process inputs.
XW-EDA-PRO
The XW-EDA-PRO variants adds 2 Discrete Open Drain Digital Inputs / Outputs on a 4 Pin M12 Male connector. These can be used to trigger alarms, monitor a switch, or control other equipment.
Easy Configuration with SYNC
SYNC by Omega allows you to configure device runtime parameters, view process values, export data, and allows you to efficiently set your XW Transmitter to operate under your preferred preferences.
Video Learning: Configure your XW Series Transmitter with SYNC Software
Specifications
Thermocouple
Type | Range | Accuracy |
---|---|---|
J | -210°C to 1200°C | 0.4°C |
K | -160°C to 1372°C | 0.4°C |
T | -190°C to 400°C | 0.4°C |
E | -220°C to 1000°C | 0.4°C |
N | -100 to 1300°C | 0.4°C |
R | 40°C to 1788°C | 0.5°C |
S | 100°C to 1768°C | 0.5°C |
B | 640°C to 1820°C | 0.5°C |
C | 0°C to 2320°C | 0.4°C |
RTD
Type | Range | Accuracy |
---|---|---|
385, 4 | Wire -200°C to 850°C | 0.3°C |
385, 3 | Wire -200°C to 850°C | 0.3°C |
385, 2 | Wire -200°C to 850°C | 0.6°C |
392, 4 | Wire -200°C to 660°C | 0.3°C |
392, 3 | Wire -200°C to 660°C | 0.3°C |
392, 2 | Wire -200°C to 660°C | 0.6°C |
3916, 4 | Wire -200°C to 660°C | 0.3°C |
3916, 3 | Wire -200°C to 660°C | 0.3°C |
3916, 2 | Wire -200°C to 660°C | 0.6°C |
Process Inputs
Type | Range | Accuracy |
---|---|---|
Current | 0-24 mA | ±10 uA |
Voltage | 0-10 V | ±5.0 mV |
Voltage | 0-1 V | ±0.5 mV |
Voltage | 0-100 mV | ±0.05 mV |
Wireless Communication
Standard: | IEEE 802.15.4, DSSS |
Frequency: | 2.4 GHz (2400 to 2483.5 MHz), 16 channels |
Network Topology: | Star topology |
Transmit Power: | 9.5 dBm |
Receiver Sensitivity: | -96 dBm |
Range: | Up to 1000 m* (3280’) outdoor and 100 m* (328’) indoor |
Power
Input Voltage: | 5 to 36 Vdc, 24 Vac +/-10% | |||
Input Power: | 0.8 W maximum | |||
Alkaline Battery: | Two C-cell 1.5Vdc (included) | |||
Lifetime: | Up to 5 years with frequency of 1 reading per 10 minutes | |||
Lithium Back-Up** Battery: | CR2032 (included) **RTC back-up only | |||
Safety Qualified AC Power Adaptor (optional): | ||||
Nominal Output: | 5 Vdc @ 0.6 A | |||
Input: | 100 to 240 Vdc, 50/60 Hz | |||
Operating Temperature: | 0 to 40 °C (32 to 104°F) |
Environmental
Operating Conditions: | ||||
Base Unit: | -20 to 70 °C (-4 to 158°F), 90% RH non-condensing | |||
CR2032 Battery: | -20 to 60°C (-4 to 140°F), 90% RH | |||
Alkaline Battery: | -18 to 55°C (-0.4 to 131°F), 90% RH non-condensing |
Mechanical
Enclosure Material: | Polycarbonate |
Enclosure Protection: | NEMA 4 (IP65) |
Enclosure Dimensions: | 135.9 L x 82 W x 39 mm D (5.35 x 3.23 x 1.56”) |
General
Agency Approvals: | ECCN, EAR99 EMC 2014/30/EU, LVD 2014/35/EU, RED 2014/53/EU |
Software: | Compatible with SYNC and OEG) |
Compatibility | Thermocouple, RTD, and Process |
Rated 2 out of
5
by
SSmith from
Pairing with Receiver is 50/50
1 transmitter paired with the receiver, but the 2nd transmitter will not.
Date published: 2021-03-26
Rated 1 out of
5
by
MPowers from
DOESN'T WORK ACCURATELY WITH 2 THERMOCOUPLES!!!!
Doesn't work with 2 thermocouples. Purchased 10+ of these units to track process conditions in the plant. Had to convert the mV to mA with signal conditioners to use 2 thermocouples on the same transmitter.
Date published: 2021-02-08
- RoHS 2015/863 - Voir le certificat
- Approuvé CE
Had the XW-EDA unit a M12, 4 pin, female connector?. In that case the process sensor must to have a wire with a M12, 4 pin, male connector?
Thank you for your question. The XW-EDA is a m12 4-pin male connector. You simply have to purchase M12-S-F-FM and attach wires or simply use a connector with wires M12C-PUR-4-S-F-5
Date published: 2020-08-06
Can I use Er34615 and Er26500 primary batteries?
Thank you for your question. We will require more information to help on this question, please email the DAS team at DAS@OMEGA.COM
Date published: 2023-09-20
Can this unit be powered by an external power supply? If so, does OMEGA manufactures/supplies the external power supply?
Hello Jorge
Yes it can be powered by 5 to 36 VDC power supply, one of the ones we sell is UNIV-AC-100/240-5-M8.
Date published: 2020-01-09
1: Wireless Coordinator/Receiver and Optional External Power Supply
2: M12 TC Probes
Depuis C$89.45
0 In Stock
Depuis C$56.64
0 In Stock
3: M12 TC Cables and Connectors - Note: A cable is required for TC Probe connection to XW-EDA
Depuis C$39.00
0 In Stock
4: M12 RTD Probes
Depuis C$160.05
0 In Stock
Depuis C$60.63
0 In Stock
Depuis C$67.55
0 In Stock
5: M12 RTD Cables and Connectors - Note: A cable is required for RTD Probe connection to XW-EDA
6: M12-4 Accessories -PRO Models Only
M12, 4 pin Straight socket to stripped leads cable - 10m
C$100.48
0 In Stock